Exide Sprinter S12V4500PP lead-acid battery with 12 V and 120 Ah
Description
Product information
The Exide Sprinter S12V4500PP is a high-performance, maintenance-free VRLA-AGM lead battery specifically developed for high-current discharges in short bridging times. It is the ideal energy solution for uninterruptible power supplies (UPS systems) and other critical emergency power applications where maximum reliability and high power density are required. With a nominal voltage of 12 V and a high capacity of 120 Ah, it offers a reliable energy reserve for crucial moments.
Highlights at a glance
- High power density: Optimised for high-current discharges in short periods.
- Long service life: 10 to 12 years design life according to EUROBAT classification.
- Maximum reliability: Ideal for UPS systems and critical emergency power applications.
- Maintenance-free (VRLA-AGM): Sealed design, no need to refill with water.
- High capacity: 120 Ah for a safe and long-lasting energy reserve.
Powerful in critical applications
The Exide Sprinter series is the proven choice for systems where a power failure would have serious consequences. The S12V4500PP ensures uninterrupted power supply in data centres, telecommunications systems, hospitals, power plants and industrial control systems. Its ability to deliver very high currents in a short time makes it indispensable for bridging network failures until emergency generators take over the supply.
Proven AGM technology for the highest requirements
The AGM technology used (Absorbent Glass Mat), in which the electrolyte is bound in a glass fibre fleece, ensures very low internal resistance and excellent high-current capability. The valve-regulated, sealed design (VRLA) prevents gas leakage during normal operation and allows installation in any position (except upside down). This ensures a high level of operational safety and makes the battery absolutely maintenance-free.
Reliability and durability in the system
The S12V4500PP is designed for maximum operational reliability and a long service life in standby parallel operation. Its classification according to EUROBAT promises a service life of 10 to 12 years under ideal conditions. The robust housing made of impact-resistant plastic and the high-quality internal components guarantee reliable performance over many years and make the battery an economical solution for professional systems.
Characteristics
| Model | Exide Sprinter S12V4500PP |
| Battery type | VRLA AGM (High-Rate / UPS) |
| Nominal voltage (V) | 12 |
| Capacity (Ah) | 120 (at 10h rate) |
| Short-circuit current (A) | 4500 |
| Charging voltage (float charge) | 13.62V (at 20°C) |
| Charging voltage (boost charge) | 14.1V |
| Operating temperature (°C) | Charging: 0 ~ 40 / Discharging: -20 ~ 50 |
| Storage temperature (°C) | -20 ~ 40 |
| Service life | 12 years (EUROBAT: High Performance) |
| Dimensions (L/W/H, mm) | 407 x 173 x 240 |
| Weight (kg) | approx. 42.0 |
| Connection | M8 screw terminal |
| Certifications | ISO 9001, ISO 14001, UL |
FAQs about the Exide Sprinter S12V4500PP
What is the main area of application for the Exide Sprinter series?
The Sprinter series is specially designed for high-current applications over short periods. Their main application area is, therefore, uninterruptible power supplies (UPS systems) in data centres, industrial plants, and other critical infrastructures.
What does "10 to 12 years design life according to EUROBAT" mean?
This is the expected service life of the battery under ideal standby conditions (e.g. constant ambient temperature of 20 °C, correct charging voltage). The actual service life may vary depending on operating conditions such as temperature, charge cycles, and depth of discharge.
Can I connect several of these batteries together?
Yes, to build larger battery systems, several batteries can be connected in series (to increase the voltage) or in parallel (to increase the capacity). It is essential to use only identical batteries of the same type, age, and state of charge for this purpose.
How should this battery be charged?
For maximum service life in standby mode, a professional charger or a UPS system with an IUoU charging characteristic and temperature compensation should be used. The exact charging voltages are specified in the manufacturer's data sheet.
Properties
| Capacity: | 120Ah |
|---|---|
| Connections: | M6 |
| Item number: | EXIS12V4500PP |
| Tension: | 12V |
Documents 1